Application Notes  Caution    BACK 
  Signal line and telephone line surge protection  

 Switching surge protection 

 Semiconductor protection and Contact park suppression

    Line protection¡@

¡@

    Line to Line Protection Connections

        Line to Line

¡@
Symbol Line Voltage Varistor Voltage
V1 DC 12V 22V
DC 24V 39V
AC 100V 200V,220V,240V*,270V*
AC 120V 240V,270V*
AC 127V 270V
AC 200V 390V,430V,470V*
AC 240V 430V,470V*
V3 AC 240V 430V,470V,510V
AC 265V 510V
AC 380V 820V
AC 415V 910V
AC 460V 1100V
AC 480V 1100V

Notes

 1.Maximum operating voltage shall be lower than Maximum allowable voltage of Varistor at any time

 2.Varistor with * are recommended for single phase, 3 wire applications to withstand a temporary overvoltage caused by unbanlance load.

¡@

Line to Line to Ground Protection Connections ¡@

Line to Ground

¡@
Symbol Line Voltage Varistor voltage
V2 AC100V to 220V 430V,470V
AC240V

430V,470V

or 750V* *

or higher Varistor Voltage

or 1800V* * *

V4 AC240V

430V,470V

or 750V* *

or higher Varistor Voltage

or 1800V* * *

¡@

Notes

 1.When the 500V insulation resistance test of the circuits employing Varistor is conducted, We shall be remove after getting approval from the customer, or * * with the Maximum Allowable Voltage exceeding to test voltage shall be used.

 2.When the 1000V withstanding voltage test is conducted, We shall be removed after getting approval from the customer according to the relevant regulations, or * * * with the Maximum allowable exceeding to the test Voltage shall be used.
 3.To avoid Varistor failure caused by the ground fault, We with higher Voltage listed in the table shall be used for the AC 120V line to ground application.