| Signal line and telephone line surge protection |
Semiconductor protection and Contact park suppression |
|||||||||||||||||||||||||||||||||
|
Line protection¡@ |
¡@ |
|||||||||||||||||||||||||||||||||
|
Line to Line Protection Connections |
Line to Line |
|||||||||||||||||||||||||||||||||
|
|
¡@ |
|
||||||||||||||||||||||||||||||||
|
Notes 1.Maximum operating voltage shall be lower than Maximum allowable voltage of Varistor at any time 2.Varistor with * are recommended for single phase, 3 wire applications to withstand a temporary overvoltage caused by unbanlance load. ¡@ |
||||||||||||||||||||||||||||||||||
| Line to Line to Ground Protection Connections | ¡@ |
Line to Ground |
||||||||||||||||||||||||||||||||
|
|
¡@ |
¡@ |
||||||||||||||||||||||||||||||||
|
Notes 1.When the 500V insulation resistance test of the circuits employing Varistor is conducted, We shall be remove after getting approval from the customer, or * * with the Maximum Allowable Voltage exceeding to test voltage shall be used. |
||||||||||||||||||||||||||||||||||
| 2.When the 1000V withstanding voltage test is conducted, We shall be removed after getting approval from the customer according to the relevant regulations, or * * * with the Maximum allowable exceeding to the test Voltage shall be used. | ||||||||||||||||||||||||||||||||||
| 3.To avoid Varistor failure caused by the ground fault, We with higher Voltage listed in the table shall be used for the AC 120V line to ground application. | ||||||||||||||||||||||||||||||||||